    防火卷帘门的基础调试内容包括哪些?
    来源:http://www.xmyzcy.com   时间:2019-9-11 20:49:19

    防火卷帘门在安装完之后,为了保证有一个良好的使用情况,我们应该对防火卷帘门进行功能测试,检查是否满足要求。下面济南卷帘门的小编就给大家总结一下防火卷帘门的基础调试内容!

    After installation, in order to ensure a good use, we should test the function of the fire-proof rolling shutter door and check whether it meets the requirements。 Next Jinan roll curtain door to summarize the basic debugging content of fire-proof roll curtain door!

    1。通电功能测试

    1。 Power-on Function Testing

    将防火卷帘控制器分别与消防控制室的火灾报警控制器或消防联动控制设备、相关的火灾探测器、卷门机等连接并通电,防火卷帘控制器应处于正常工作状态。

    Connect and electrify the fire curtain controller with the fire alarm controller or fire linkage control equipment of the fire control room, relevant fire detectors and door rolling machine respectively. The fire curtain controller should be in normal working state.

    2.备用电源测试

    2. Test of Standby Power Supply

    设有备用电源的防火卷帘,其控制器应有主、备电源转换功能。备用电源的电池容量应保证防火卷帘控制器在备用电源供电条件下能正常可靠工作1h,并应提供控制器控制卷门机速放控制装置完成卷帘自重垂降,控制卷帘降至下限位所需的电源。

    Fire-proof roll curtain with standby power supply, its controller should have main and standby power conversion function. The battery capacity of the standby power supply should ensure that the fire-proof shutter controller can work normally and reliably for 1 hour under the condition of standby power supply, and the power supply needed by the controller to control the speed-release control device of the door-rolling machine to complete the self-weight sag of the shutter and control the shutter to the lower limit should be provided.

    济南卷帘门

    3.火灾报警功能测试

    3. Fire alarm function test

    防火卷帘控制器应直接或间接的接收来自火灾探测器组发出的火灾报警信号,并应发出声、光报警信号。

    Fire curtain controller should receive fire alarm signal from fire detector group directly or indirectly, and should send out sound and light alarm signal.

    4。故障报警功能测试

    4. Fault Alarm Function Testing

    防火卷帘控制器的电源缺相或相序有误,以及防火卷帘控制器与火灾探测器之间的连接线断线或发生故障,防火卷帘控制器均应发出故障报警信号。

    The power supply of the fire curtain controller is out of phase or the phase sequence is wrong, and the connection between the fire curtain controller and the fire detector is broken or malfunction。 The fire curtain controller should send out the fault alarm signal。